It’s like a clear poly froze wherever it goes outside. This caused pressure in the line which caused the clear poly to come off of the condensate pump. At this point, the water probably sprayed out of the condensate pump got all over the decking and filled up the emergency drain pan. Once it filled up the emergency drain pan float switch shut off the furnace. The emergency drain pan is 100% block of ice. I reconnected the hose made sure the hose clamp was super tight started the system to make sure it would come on, and I turned off the breaker the condensate pump and all the ice in the emergency drain pan will have to melt before we can run the system. Gonna have to vacuum out the water, reconnect the float switch inside the furnace and test to make sure there’s no other issues