Water in emergency drain pan. Put my level on the air handler and it was pitched toward the back of the unit away from the drain. Main adjustment to the pads under the unit so it has pitched toward the front. Pulled the filter door off the unit and shine my light as system. Didn’t see any evidence of water dripping over the drain pan took the drain pipe out of the condensate pump and put the PVC pipe into a clear water bottle to see it drain. Filled up the water bottle pretty fast still didn’t see any evidence of water dripping past the drain pan. I think the drain pipe that went into the condensate pump went in just a little bit too far causing the PVC pipe to have a double trap. Went ahead and cut the drain pipe down so it just barely enters the compensate. Let the system run. Seems like it’s draining fine now. Double checked through the filter door one more time to verify that I couldn’t see any water dripping off the coil drain pan.