Returned 7/8/25 removed water from auxiliary drain pan - allowed unit to cycle on - ran water through system primary drain pan through drain - condensate pump cycles normally - blocked primary drain port and filled primary drain pan with water and watched - found drain pan drips in back left corner of primary drain - recommend replacement of drain pan - will follow up with availability of drain pan.