Found indoor blower motor capacitor had failed (measured 0 mfd) causing outdoor unit to shut off on thermal lockout. Noted blower wheel motion on motor shaft was tight but motor and wheel still can spin freely. Replaced capacitor and cycled system to check operation. Blower motor amps 2.1 Temperature rise 20-35 Electric heat amps 40 Everything came back on and runs normally again!