Upon arrival, I found the blower motor running none stop with the thermostat off and fan set to auto. I proceeded to the attic and checked my voltage at the motor. I confirmed that I have my 240v to power the motor. I removed the 24v speed wires from the motor and it still continuously ran. This indicated that the motor control module is faulty causing the motor to stay on without a speed voltage call. I reached out to shearer supply and ordered the motor. The system is not down and heating at this time,

Upon arrival, I found the blower motor running none stop with the thermostat off and fan set to auto. I proceeded to the attic and checked my voltage at the motor. I confirmed that I have my 240v to power the motor. I removed the 24v speed wires from the motor and it still continuously ran. This indicated that the motor control module is faulty causing the motor to stay on without a speed voltage call. I reached out to shearer supply and ordered the motor. The system is not down and heating at this time, Upon arrival, I found the blower motor running none stop with the thermostat off and fan set to auto. I proceeded to the attic and checked my voltage at the motor. I confirmed that I have my 240v to power the motor. I removed the 24v speed wires from the motor and it still continuously ran. This indicated that the motor control module is faulty causing the motor to stay on without a speed voltage call. I reached out to shearer supply and ordered the motor. The system is not down and heating at this time,