824 S Central Expressway, Suite 100
Anna, TX 75409
903-482-4900

Local Reviews
for prosper, tx

Rated 5.0 out of 5 stars based on 2 customer reviews

Great Work

I am very happy for the duct cleaning service provided by Adon Complete. They provided lots of details, explanations, suggestions they provided and they did great work. I would recommend for duct cleaning.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great job

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for prosper, tx

Jacob P.

Jacob P. Job Checkin

Arrived on site, customer stated ac was putting out warm air and not cooling the upstairs. Upon initial inspection, it was noticed there was rust in the emergency drain pan. Indicating that there is or was water not draining properly. It was found that the refrigerant pressures were very low. Suspected coil leak. Found leak in evaporator coil on the back side. Recommended coil replacement to restore systems cooling functionality. Customer decided to go forward with the repair. Deposit collected, will pick up coil today and schedule return date to complete repair. Est time for repair is Tuesday -Wednesday.


Shelby S.

Shelby S. Job Checkin

Performed single system cooling maintenance. I checked amps, filter, electrical, drains, cleanliness, temperature differential, refrigerant temperature, and washed the outdoor unit. The system is performing within manufacture specifications. To prepare the drain for cooling season, it is advised to perform a drain treatment. This is an attempt to prevent clogging from occurring. Customer said that her allergies have been bothering her lately and that the filter probably just needs to be changed. Upon observation, it was determined that the filter has minimal build up. I replaced the filter. I offered to upgrade the filtration and an air cleaning device (air scrubber).


Cesar  O.

Cesar O. Job Checkin

Previous visit we found the #2 system (downstairs) frozen,,, we were not able to finish the spring maintenance ,, we were not sure if this was caused by the extremely dirty return filter we found or low on refrigerant,, today we checked refrigerant pressures, measured temperature differential in cooling mode and unit was working properly. We will send estimates for recommendations ( for downstairs/ upstairs)


Jacob P.

Jacob P. Job Checkin

Performed a 3 system spring maintenance ( gas). Tasks performed. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motors. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked refrigerant pressure,,, downstairs unit is frozen ,,we need to come back and check again, issue might be caused by extremely dirty filter or low on refrigerant. 7. Checked compressors amp draw. 8. Checked condenser fan motors amp draw. 9. Inspected / replaced return filters,,, all 3 systems had extremely dirty filter . 10. Inspected return plenums for debris/ dirty,,,upstairs/ downstairs units are very dusty, highly recommend a duct cleaning. 11. Inspected evaporator coils. 12. Inspected blower motor/ blower wheels,,, downstairs/ upstairs are very dusty, highly recommend a blower cleaning. 13. Checked blower amp draw. 14. Measured temperature differential ,, temperature differential on the ups


Shelby S.

Shelby S. Job Checkin

Performed 2 system cooling maintenance. I checked amps, capacitors, filter, cleanliness, electrical, drains, temperature difference, refrigerant temperature, and safeties. The systems are cooling good, I did notice some issues. The main unit’s contactor is burning up. It has huge burn spots and the ohm value tested out of typical range. The 45/7.5 capacitor tested bad as well. It is reading 40/7. It is recommended both be replace to ensure proper function through the summer. The other unit’s capacitor is reading out of range. It is rated for 30/3 and is reading 26/.06. With these numbers, it is highly likely of a failure occurring soon. The blower motor has build up present. This adds stress to the blower motor and can result in premature failure.


Cesar  O.

Cesar O. Job Checkin

Performed a 1 system spring maintenance ( gas). Tasks performed. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked refrigerant pressures were. 7. Checked compressor amp draw. 8. Checked condenser fan motor amp draw. 9. Inspected / replaced return filter. 10. Inspected return plenum for debris/ dirty. 11. Inspected evaporator coil. 12. Inspected blower motor/ blower wheel. 13. Checked blower amp draw. 14. Measured temperature differential . 15. Inspected drain lines. 1. Washed condenser unit.


Jacob P.

Jacob P. Job Checkin

Arrived at our clients home for two system heat maintenance inspection. Our client provided me with new filters to be replaced today. Once the filters were replaced at proceeded to test and inspect the fire safety shut off for both units. I clean both flame sensors, pressure switch ports, and furnace cabinets for both units. Our client is in the process of selling her home and I mentioned that the downstairs older unit may need a sediment trap added to the gas line for the furnace. To have this installed today to help bring the furnace up to code. As a courtesy also I did cut back some roof Material that was close to the flue pipe of the furnace. Everything is working and heating properly on departure.


Shelby S.

Shelby S. Job Checkin

Found the system popping the fuse in the cooling cycle. I investigated the outdoor unit and found a shorted contactor. I replaced the contactor and tested the unit. The unit is back to being fully operational and cooling to manufacture specifications.


Alex G.

Alex G. Job Checkin

Form system maintenance on 2 systems both systems are from 2003 systems. System #2 requires gas code upgrade, capacitor for indoor blow motor and outdoor condensing unit, unit also needs a P-trap with a secondary float switch to any water leaking onto emergency drain pan, emergency drain pan 30 x 30 System #1 requires a gas upgrade sediment trap. P-trap for the condensation line with an emergency float switch , a secondary drain pen 30 x 30 a capacitor for the indoor blower motor.


Shelby S.

Shelby S. Job Checkin

Performed two system heating management. Checked amps, electrical, safeties, cleanliness, drains, and filter. System is performing to manufacture specifications in heating. Recommendations 1. Filtration of both systems are poor. I recommend converting it over to a Aprilaire filter. This will help keep the ducts, blower, and evaporator coil cleaner. 2. Both systems have dirty blowers. This causes the motor to have to work harder and will ultimately lead to a prematurely failed blower motor.


Jerad L.

Jerad L. Job Checkin

Came out for 2 system maintenance. Our installs 1 yr old gas systems. Started by turning heat up at tstats. Once engaged checked all heating elements to verify proper heating sequence. Burners are firing properly, safeties are operating as designed. Filters were extremely dirty causing units to over condensate. Changed out filters (20x25)&(16x25) Return ducts are extremely dirty however rest of ducts are still in good condition recommend duct cleaning to keep systems in top condition as well as adding surge protection to protect against power surges. Thank you for your time and allowing me into your home.


Shelby S.

Shelby S. Job Checkin

Found downstairs low on R410a but not as severely as the u/s system. Offered to add refrigerant and customer declined at the time of service. Provided pricing to replace both evaporator coils.


Shelby S.

Shelby S. Job Checkin

Found system low on R410A. Located a leak in the evaporator coil. I had the office run the warranty and confirmed it is under warranty until 2028. Provided pricing to replace evaporator coil.


Sam M.

Sam M. Job Checkin

Fall PM- Checked: blower motor and wheel, electrical wiring and connections, limit switches and safety controls, airflow, filters, temperature rise, thermostat, amp draws, capacitor, gas line and connections, (no gas leaks), gas flow, burners, orifices, ignitor, heat exchangers, and flame quality. The flame sensor was cleaned.    


AC technician A.

AC technician A. Job Checkin

Came out today for 1 system maintenance. Upon arrival started with outside inverter system, checked all electrical components and washed outside unit. Coil fins are clean and in good condition, no signs of burn marks. Surge protection is operating as designed. On indoor air handler checked all electrical components all components are in good condition with no signs of burn marks. Filter was just changed 20x25x4, ducts are clean as well as ecm motor and wheel is clean from last visit. Only recommendation I have is to add pan treatment into system to keep drain lines clear. Thank you for your time and allowing me into your home.