He is very polite and patient. Explains all the options I have and provided great service. Thanks!
Our A/C broke when the weather started to get hot. We called Adon Complete, and Charles came. He was experienced and professional. He and his crew replaced our 20-year old unit, and our system is up and running just in time for summer. I would recommend Adon Complete for all my friends and neighbors.
Objective: To install an exhaust fan in the ceiling of the media room closet to help ventilate and cool the area containing high-performance AV equipment. The goal is to pull cooler air through the closet and discharge hot air into the attic space, preventing overheating and maintaining optimal equipment performance. ⸻ Work Description: 1. Exhaust Fan Installation • Install a high-performance exhaust fan in the ceiling of the media room closet. • The fan will pull cooler ambient air through the closet and discharge the hot air into the attic space above. • Installation will ensure minimal noise and vibration while maximizing airflow. 2. Thermostat and Controls • Install a wall-mounted thermostat in the closet to control the exhaust fan based on temperature. • Thermostat will not adjust room temperature but will act as a temperature-sensitive switch for the exhaust fan. • System will include a relay and a low-voltage transformer to operate the fan based on thermostat readings
Upon arrival the office staff said the ac was not cooling but the fan was running. We proceeded to the riser room to gain roof access. Upon inspection of the unit we found that the compressor and coils were frozen over. We are unable to determine the issue until unit can thaw out and we can properly diagnose the issues. Spoke to the owner and confirmed we would need to come back in the morning. Unit was not cooling but fan was running upon departure.
Arrived on site customer complained of theater room getting too warm and daughters bedroom getting too cold. Adjusted airflow as best we could to push more air to theatre and slightly less to daughter’s room. Closed off damper to upstairs main area with thermostat. May need an additional supply and larger return to accommodate customers preferences. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked compressor amp draw. 7. Checked condenser fan motor amp draw. 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Inspected blower motor/ blower wheel. 12. Checked blower amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Inspected drain lines and treated to prevent blockages 15. Washed condenser uni
1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked compressor amp draw. 7. Checked condenser fan motor amp draw. 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Inspected blower motor/ blower wheel. 12. Checked blower amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Inspected drain lines and treated to prevent blockages 15. Washed condenser unit to promote heat exchange Upstairs unit bad compressor capacitor. Informed customer of possibility of unit failure due to capacitor failure. Customer wanted to monitor the capacitor and proceed if it gets worse or fails. Notified customer of temperature sensor with dead batteries. Customer replaced batteries error went away.
I arrived at our clients home for the unit not cooling properly. I was first led into the home and into the attic. Everything appeared to be working properly and the filter was in good condition. I then went outside and found the outdoor compressor not running. I further diagnosed a failed capacitor to the compressor motor. I did further test the contactor and ensured the system had standing refrigerant. I showed my findings to Mr Adam’s and we discussed the capacitor replacement as well as adding a compressor saver tot he outdoor unit today. Mr Adam’s elected to replace the capacitor only today. Once replaced I further tested and the system to ensure proper operation. I did measure a good 20° drop in the attic. The compressor however is exceeding is manufacturing amp limit. It started up at 166 out of 146 amps today. I did a lite rinse of the outdoor coils to also help the system breathe and operate better. The Freon pressures are a little low. Mr Adam’s is aware this R22 refriger
I arrived at our clients home to preform a single system cooling maintenance. I went through and answered Mr Obryan’s questions regarding the maintenance and what we provided in the cooling and heat in services. We first proceeded into the attic and did a visual inspection on the AirHandler. I then went outside and began to test all the electrical components on the outdoor heat pump. I first rinsed the outdoor coils with water. After that I found several components with visible signs of failure and also were reading close to failure according to manufacturer specifications. I went back into the attic and checked the temperature drop at the air handler. Mr OBryan had several windows and doors open when checking refrigerant pressures and temperatures but I was still getting a 17° drop. I went back into the attic and tested the electrical components for the AirHandler. I found another compromised contactor and a capacitor that failed my test today. I showed all my findings to our client
I found the upstairs unit low on R410a. I called and received approval to install leak seal and 5 pounds of R410a. System is now cooling and dropping temperature upstairs.
Performed a 2 commercial system spring maintenance ( heat pump). Tasks performed. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor,,,condenser fan capacitor on both units are failing,,7.5/5.0 MFD ,, they need to be replaced as soon as possible,,, we also recommended to install a hard start kit on both units , it will extend the life and stress on the compressor. 6. Checked refrigerant pressures. 7. Checked compressor amp draw. 8. Checked condenser fan motor amp draw. 9. Inspected / replaced return filter,,filters are very dirty,customer will replace them later 10. Inspected return plenum for debris/ dirty. 11. Inspected evaporator coil,,unit #2 is extremely dirty, had 11 degrees split differential, evaporator needs to get cleaned as soon as possible. 12. Inspected blower motor/ blower wheel,,,unit #2 is extremely dirt
Arrived for a single system unit replacement estimate. Our client is looking for either a single stage or 2 stage system upgrade in his home. There would be additional return vents required for the new system options. We will also include a duct cleaning service to be preformed with the new equipment installation as well as surge protection on both indoor and outdoor equipment.
1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked compressor amp draw. 7. Checked condenser fan motor amp draw. 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Inspected blower motor/ blower wheel. 12. Checked blower amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Inspected drain lines and treated to prevent blockages 15. Washed condenser unit to promote heat exchange Found high start amps on Amana unit as well as a bad contactor. Also noticed high start amps on Trane unit Filter 416 missing
Performed a 1 system spring maintenance ( gas). Tasks performed. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked refrigerant pressures. 7. Checked compressor amp draw. 8. Checked condenser fan motor amp draw. 9. Inspected / replaced return filter. 10. Inspected return plenum for debris/ dirty. 11. Inspected evaporator coil. 12. Inspected blower motor/ blower wheel. 13. Checked blower amp draw. 14. Measured temperature differential . 15. Inspected drain lines. 16. Washed condenser unit. 17. Tested contactor.
Returned today to remove and replace the failed indoor blower motor. Once replaced I tested the unit to ensure proper operation and cooling. The unit is cooling with a 20° drop and has a clean filter. I asked our client regarding any surges in power or blackouts and he is unaware of anything recent. I did create and send an estimate for a surge protector and a blower wheel cleaning for the downstairs unit. The unit is cooling properly on departure.
I arrived at our clients home for a duct cleaning estimate. I proceeded into the attic and found all 3 attic units all from 2003. I opened the cabinets to all 3 units to assess the level of dust accumulated in the duct work and also on the blower motors. The upstairs and main area unit motors have evidence of oil leaking from the motors and a significant amount of dust accumulated on them. I included removal and cleaning the blower wheels to the estimate for all 3 systems. Our client is aware that the motors may fail after the cleaning due to the age and stress caused by the dust build up.
Performed 2 system cooling maintenance. I checked amps, capacitors, filters, electrical, drains, safeties, cleanliness, temperature split, and ducts. The systems are both cooling great. However, the ducts has had some major damage caused by critters. The supply plenum has been eaten through by approximately 80%. There are multiple ducts that have had their insulation eaten exposing the inner liner. There are ducts that have had the inner liner punctured and deemed not repairable. I provided pricing to patch what we can with a roll of insulation and flex tape, replace a 5” and 9” duct on the upstairs unit, and replace the plenum on the upstairs unit.
Upon arrival client stated that the unit was not cooling. We proceeded to the thermostat to turn on the unit. We noticed that the indoor blower motor was not coming on. We checked the outside unit and the compressor and fan were running as they should. We checked the inside blower fan motor voltage on the high and low side of the plugs. The voltage readings for high and low voltage were reading within range but when plugged into the motor, the motor would not start. We determined the blower motor was bad and needed a replacement. Verified that the unit was not under warranty. Offered replacement estimate to the client. Client elected to go forward with the repair. Upon departure we left the downstairs unit off until blower motor is replaced. Motor is ordered with the manufacture should be available for pickup to tomorrow. Will call and communicate with homeowner to schedule replacement.