Arrived on site, customer stated all was well with system. Although, she had not run the cooling yet for the year. Began evaluation of system on the outdoor condenser. Contactor tested within range, and compressor start as well as run amps were within specs. The outdoor fan however, was showing high start amps. Which could indicate that the motor is close to failing. At the indoor unit I noticed some corrosion in the emergency drain pan that could have been from previously. Noted previous work blowout valve will continue to monitor. No water safety switch on primary drain line. Blower start and run amps tested within range. Return and supply split 20 degrees. System left in good working condition. Recommendation 1. Air Scrubber-to assist in cleaning the air in the home through ionization of dust particles so that more is captured by the filter as well as kill growth around the coil