Preformed dryer vent cleaning, Preformed 2 system heat pump heating maintenance. I tested all electrical components for the upstairs and down stairs units. All electrical on the i side equipment tested within manufacturer specifications. I proceeded to test all electrical components and start amps on the compressor. I found that on the upstairs unit the capacitor and Contactor were failing. Also the unit was starting up at 60 amps out of 59 amps. I also found that on the downstairs unit the start amps were over 100 amps. Client elected to have compressor saver bundle installed on the upstairs unit and a hard start kit installed on the downstairs unit. Both units are heating upon departure. -Contactor -Turbo Multi Use Capacitor - 5-2-1 Hard Start Kit x 2