I performed a complimentary heating check-up on 2 systems. I discovered that the lennox system needs a hard start due to pulling 67/71 amps on start up. I observed that neither system has surge protection. I would highly advise that at least one be put on the carrier system. The unit is a carrier infinity and has a big control board in the outdoor unit. These boards are susceptible to surge damage. Units are heating upon departure.

I performed a complimentary heating check-up on 2 systems. I discovered that the lennox system needs a hard start due to pulling 67/71 amps on start up. I observed that neither system has surge protection. I would highly advise that at least one be put on the carrier system. The unit is a carrier infinity and has a big control board in the outdoor unit. These boards are susceptible to surge damage. Units are heating upon departure. I performed a complimentary heating check-up on 2 systems. I discovered that the lennox system needs a hard start due to pulling 67/71 amps on start up. I observed that neither system has surge protection. I would highly advise that at least one be put on the carrier system. The unit is a carrier infinity and has a big control board in the outdoor unit. These boards are susceptible to surge damage. Units are heating upon departure.