Diagnostic/ System blowing air but not cooling. I arrived and turned the thermostat on in cool mode. I verified indoor airflow and went outside. I found nothing running at the condenser. I had the right high voltage and low voltage at the contactor but the system was not running due to a failed capacitor. I replaced the capacitor and got the compressor to come on but not the fan motor. The fan motor was overheated, so I hosed it down for a few minutes. I fired the system off and the motor came on. After 10 minutes of run time, its amperage is within factory specs (1.36 out of 1.40 amps). The system is cooling properly at this time.