Today, I arrived on site to perform a winter maintenance check on the HVAC equipment. Overall Equipment Condition: * Good condition noted for both indoor and outdoor units. Indoor Unit Details: * Located in a closet as an air handler. * Services the whole home. * Filtration system is a pleated 1" filter. * Customer declined filters and will provide their own. * Filter size is (2) 14x20x1. * Indoor coil is clean and in good condition. Outdoor Unit Details: * Located on the side of the house as a heat pump. * Outdoor coil is clean and in good condition, cleaned today. Electrical Components: * All tested components are functioning properly within manufacturer specs: * Blower Motor * Heat Strip Kit * Condenser Fan Motor * Compressor * Blower Run Capacitor * Compressor Run Capacitor * Fan Run Capacitor * Contactor * Defrost Control Board * Electrical Wiring Inspections: * Blower Wheel, Electrical Wires, and Primary Drain Pan are in good condition. * No components fo