Brennan worked around my schedule and came out on Sunday!! Very knowledgeable and honest!! Would highly recommend! Been a property manager for over 20 year and have never seen such prompt and honest service! Thank you!!
System is too old for balancing gave quote for a new system. She will like more likely be financing.
Today we returned to the home for: - Replacement of the blower motor and module
Today we visited to determine why the AC unit is not working. Sharleen mentioned she felt cold air coming out of the wrong vent (return). We found the unit to have a failed blower motor/module. The total repair for the replacement motor and programmed module is $832.56.
Upon arrival unit was running low in refrigerant sub cooling was 0.4 added two pouf Freon increase sub cooling unit is running in cooling. Unit was install Last July I was no sure if still under warranty.
Brennan G Today I visited for the downstairs thermostat going blank. Before arrival Effie had reset power to the system and the thermostat came back on and the equipment started working again. I preformed basic checks and everything is in proper working order. I treated the drain lines with drain cleaner, both systems are operating normally at this time.
- Replacement of the system dual capacitor - Replacement of the condenser fan motor
Today we visited because the upstairs system was not cooling. We learned the outside fan was not working properly. The dual capacitor was bad. After replacing the capacitor the fan still wouldn’t work unless pushed to get started. The unit requires a 5mfd capacitor for the fan but wouldn’t start so James installed a 7.5mfd and the system cycled on its own. There is a high probability of the fan motor failing soon. Peter decided to have both the capacitor and fan motor replaced. We will call tomorrow to arrange the repair.
This system uses a variable speed outdoor compressor and fan, the condenser will “throttle” its cooling output based on the amount of cooling required. The Blower motor is a single speed. 10 year Parts warranty through manufacture 10 year Labor warranty through gap coverage 1st year maintenance includes Both systems will have 5kw electric heaters Job Includes: All required permits and inspections Any required code upgrades Any necessary breaker changes Pearl certificate New float switches Drain line flush New return box liner for upstairs return Emergency pan and float for upstairs return Line-set flush Duct sanitation Surge protectors Ultraviolet Lamps New air handler decking New thermostats Job is being funded through synchrony 25months 0% Interest $17,000 is being funded $3248.28 is being payed down , collected today via check.
Brennan G Today I visited for a system replacement estimate. Effie elected to have both systems replaced with 15SEER Bosch heat-pump inverters Job total is $20,248.28. $17,000 has been funded through synchrony 25months 0% Interest. The remaining $3248.28 was payed via check today.
Today, upon arrival, the owner was not present. A woman was home. That stated the owner was looking at another house. The unit had a tripped float switch and clogged drain line. James cleaned the drain line. There was fresh evidence someone else had recently attempted to clear the drain. James mentioned this to the person at house and she spontaneously remembered someone else had come today. Sandra has not answered any calls or texts. The service fee cannot be emailed to Sandra because we do not have her email.
Brennan G Todays visit was to check the system before inspection. The breakers are the correct size and the system is cooling/draining normally.
Brennan G Todays visit was for the system not cooling. Found the terminals had blown out of the compressor The system is a 2004 Lennox R22. Due to repair cost Jim decided it would be better to replace the system versus repairing it 3.5 Ton Goodman scheduled to be installed tomorrow. This it’s the most basic equipment available for purchase and Install today. The indoor blower and outdoor compressor are single stage. 5kw Electric heaters 10 year Parts warranty 1 year labor warranty 1st year maintenance Job Includes: All Required permits and inspections All required code upgrades New copper line-set New outdoor disconnect New hanging kit Emergency pan New drain line (3/4)1t Float switches Hurricane pad and straps Any required breaker upgrades New Honeywell thermostat t6 50% deposit Payed with card today Job scheduled for 06/02/23
Changed out filters in ah trap door in ceiling
Found low charge and bad run cap replaced run cap chose to add 3lbs of Freon 410a if Freon runs out must do leak search no warranty on Freon System up and running Repair Option
Evaporator coils are very clean. Refrigerant levels are good. Checked controls for proper operation. Homeowner says Prior filters were dirty. My thoughts are system was already iced over when filter got changed.