* No AC call. After inspection found faulty contactor and low capacitor. Replaced both parts. Then performed cleaning and wash out of condenser. Unit had not been service in a couple years and was extremely dirty. After cleaning test fan motor amperage and compressor amperage. Both of those were in accurate working condition. Checked R410a refrigerant. That too was in accurate efficiency range. After performing the clean and check and replacing faulty parts, unit is back up and running and cooling properly at this time. * customer wanted to renew maintenance agreement. One visit was used today and they will have one remaining in fall of 2024 for crawlspace furnace. *customer is requesting reminder for fall cleaning a few days before visit.