Robby D.

Robby D. Job Checkin

Performed yearly maintenance and safety checks on 2011 Lennox air conditioning system. Found 45/10 voltage absorption system reading 45/10. 67 inrush amps. 88–108 hard start reading 104. Cleaned condenser. Replaced customer supplied 18254


Josh S.

Josh S. Job Checkin

Ac check 2012 Bryant 45/5= capacitor. Filter 16-25-1

Ac check 2012 Bryant 45/5= capacitor. Filter 16-25-1

Robby D.

Robby D. Job Checkin

Performed yearly maintenance and safety checks on 22 AC system found 35/5 voltage absorption system reading 35/5 found 48 in Rush amps. Replaced 1625 one filter no issues found at this point in time.


Robby D.

Robby D. Job Checkin

Responded to no heat thermostat calling for heat. 66 in home 73 set temperature. Found code 32 for pressure switch found inducer pulling 0-3 inWC customer has exterior of home being panted. Painters covered up concentric kit not allowing proper exhaust. Removed cover per customers request to restore heat. Furnace cycled on properly without fault. 0 ppm co in supply. Dirty 16254 filter. Replaced 10/15. replaced customer supplied filter. No further issues.


Robby D.

Robby D. Job Checkin

Returned to repair. Replace blower motor and control board. Further diagnostics found identity chip faulty no allowing proper communication with blower motor. Replaced chip furnace cycled on properly. Running with 11%o2. 14 ppm co in flu. 0 ppm co in supply. 46 degree dletat. No further issues at this time.


Robby D.

Robby D. Job Checkin

Called in morning to quote for repair blower motor power choke and possible board. Replaced blower motor. New motor has different wiring connections as well as smaller plug not able to be used power choke also not able to be connected. No paperwork with blower. When installed blower would not operate from board. Will need to double check parts Monday and require at that point.


Wally T.

Wally T. Job Checkin

Annual maintenance check on a rheem air conditioner


Robby D.

Robby D. Job Checkin

Upon arrival customer stated it had started running. Found furnace running. Cycled furnace several times to find no fault occurring. Found charred/weak flame sensing system. Presented options hm15a-e. Customer chose option a. Performed repair and cycled furnace. System running with 10.5% o2. 12 ppm co in flu. 0 ppm co in supply. 45 degree deltat clean 16251 filter. Found floor drain to be clogged advised may want plumber to look at drains. Strong Oder coming from drain.


Robby D.

Robby D. Job Checkin

Performed  yearly maintenance  and safety checks on 2020 Bryant furnace in attic. Furnace is running with 10.1%o2. 9 ppm so in flu. 49 ohm igntion  system 45 degree dletat. Furnace cycled into second stage properly.system running with 7.5%o2. 33 ppmco in flu. 0 ppm co in supply. Cleaned flame sensor. Customer maintains 16254 filter. Also performed yearly maintenance  and safety checks on 20 Bryant furnace in basement. Previous  technician mentioned excess noise in motor. Found noise to be associated  with airflow in filter cabinet. After Removing filter noise stops. Furnace running with 12.4%o2. 20 ppm co in flu. 34 degree deltat. Furnace cycled into second stage properly.  Running with 7.5% o2 48 ppm co in flu. 0 ppm co in supply.  50 degree deltat.


Robby D.

Robby D. Job Checkin

Thermostat indicating call for cooling. Found code 3 for pressure switch stuck open. Reset control board. Made call for heating. Found inducer motor having issues running. Motor not seized. Seems as if something holding wheel from spinning removed motor to loom for critters. Founs bead of caulk stuck around blower wheel. Attempted to remove foreign object Unsuccessfully messed with wheel to try to free motor. Cannot remove object. Called for pricing and Availability for motor and pressure switches. Not in stock. Presented hm7 with possibility of returning for repair Tuesday or Wednesday cust9mer not ready for repair and will call next week to schedule repair.


Robby D.

Robby D. Job Checkin

Performed yearly maintenance and safety checks on 1998 Bryant furnace. Found dry bearing noise associated with inducer. Found ignition system reading 90 ohms. Also found voltage absorption system outside manufacture specifications.customer wants to wait issues out and address when fault occurs also Performed maintenance on 2017 rheem furnace. Found 40/5 voltage absorption system reading 40/5 cleaned coil. No concerns at this time.


Austin L.

Austin L. Job Checkin

Completed annual maintenance on a 2021 comfortmaker furnace. And during testing of the unit the technician found no electrical protection device, the air filter to be installed incorrectly, and ductwork to have large amounts of dust/hair build up. Customer not interested in electrical protection device at this time. Technician left fresh air corporation information for duct cleaning, as well as iwave information for air cleaner. Customer may call back at a later time for the install. Technician left filter beside unit as filter has recently been changed, and created inspection hole for combustion analysis. No issues at time of departure.


Austin L.

Austin L. Job Checkin

Completed annual maintenance on a 2021 comfortmaker air conditioner. During testing of the unit, the technician found no electrical protection device and the outdoor unit to be very dirty. Technician explained this would cause issues for the unit to keep up. Customer not interested in electrical protection device today. Technician left air filter beside unit as filter had been recently changed. No issues at time of departure.


Austin L.

Austin L. Job Checkin

No cool on a 2019 comfortmaker air conditioner. Upon arrival technician found voltage enhancement system to be dead on both sides, as well as outdoor unit to be very dirty. Technician presented options Hn13a-e. Customer chose option B. Technician replaced voltage enhancement system and installed electrical protection device. Technician cycled unit successfully after repairs were completed. 18° temperature split. No issues at time of departure.


Austin L.

Austin L. Job Checkin

No cool on a 2019 comfortmaker air conditioner. Upon arrival technician found voltage enhancement system to be dead on both sides, as well as outdoor unit to be very dirty. Technician presented options Hn13a-e. Customer chose option B. Technician replaced voltage enhancement system and installed electrical protection device. Technician cycled unit successfully after repairs were completed. 18° temperature split. No issues at time of departure.