Job Checkin

Materials added 2 cans of evaporator cleaner Notes: customer recently moved into the home and signed up for our membership program. Did a full tuneup on two systems inspected all electrical components, Freon levels, delta T, and cleared and flushed drain lines. Summary: system number 1: the high side Schrader needs to be replaced. This can cause refrigerant to leak out of the system and it is loose. The evaporator coil also has debris buildup and a level one cleaning will help remove debris and have better efficiency. System number 2: the capacitor is outside factory range. I highly suggest replacement to help prevent premature breakdown. Both systems have calcified drains. Adrian salt treatment will help prevent a clogged drain. Completed the following repairs. Replaced Schrader core on system number one high side once replaced insured. Freon levels were within. Normal range completed evaporator clean in place on the garage. Air handler completed drain solve on number two. I n