04/24/24 - Upon arrival the float was tripped, not allowing the thermostat to come on. I’ve verified refrigerant pressures and refrigerant. Pressures are within specs. I ran the system for 20 minutes and it did not begin to ice up. I also verify the starting capacitor was within specs & it was reading 38/4mf. A clogged drain line with blockage (paper towels, see pics) was found. Evaporator coils have slight microbial growth development across the coils & the outdoor coils need a deep cleaning to remove blockage across the CU coils. Recommended signing up for our Air Care Membership which includes 2x system checks per year, 20% off quoted repairs, & priority calling. Also, replacing the outdated Air Scrubber bulb. Thank you for choosing Total Air…. REPAIRS PERFORMED TODAY - Chemical drain line treatment - Air Care Membership (PD n FULL $200 today) - Evaporator clean n place