04/23/24 -Homeowner stated the thermostat goes on and off intermittently. They replaced it with a Honeywell T6 thermostat, and the problems still happened. I verified refrigerant pressures, verified that the filter was clean, and no microbial growth was across the coils, and verified the capacitor was within specs, the drain line was backed up with water in the float, which that kept tripping, making the thermostat blank. I recommended hey chemical drain line treatment be performed with pan tablets, & a drain guard installed to help treat the drain line between maintenances. Also, I recommend an electrostatic filter & a UV Kit be installed to curb the microbial growth development that can lead to clogged drain lines & costly cleanings. Thank you for choosing Total Air… 04/23/24- PART RETURN NEEDED no $$$$ is due upon completion of the part return for a chemical drain line treatment w/pan tablets. (No drain guard) Danielle LaTourm has renewed her Air Care Membership (monthly), & would