After reinstalling the parts. I rediagnosed the original problem of low voltage short. I found a section of wire exiting the wall of the house next to the line set had a splice and portion of the wire was corroded and exposising bare wire. I stripped back the wire to expose clean wire and respliced a new wire running to condenser. System is running and has been running for 45 mins without interruption.