For this job, we came out to look at a range breaker that started tripping a few months ago. Upon looking at the specs of the range, we noticed the breaker was oversized for the new appliance as well as loose connection on the range cord. Additionally, there was a multi wire branch circuit and properly terminated in the panel as it was on (2) single pole breakers rather than properly on a two pole breaker with a common trip handle. We provided multiple options for circuit repair and safety. The customer chose the Replace option. Customer declined VIP Care Plan. Replace Range receptacle Replace Range breaker as it is oversized at 50 A, the oven electrical specs call for a 40A breaker