dwayne 9am 240-535-6435 take hydro pump & adapter other parts on will call beltsville 9670658 Sprinkler Inspection FDC hydrostatic test for the (3) FDCs. This will require at least 8 HRS (2) TECHS and the following material- Hydro pump (1) 2.5" x 2" brass male adapters (3) 2" x 1" RCs (3) 1 x 1/2 bushings (9) 1/2" x 0-3 nipples (6) 1/2" ball valves (3) 1/2" Tees (3) 1/2 x 1/4 bushings (3) water gauges NOTE: Test will be performed on 3 separate FDC's Deficiency: **Sprinkler** 1. Need to install the following signs: (1) control valve sign for OS&Y on wet system in sprinkler room (1) control valve sign on incoming OS&Y in sprinkler room (3) aux drain signs for air drains on dry valves (1) air line sign in sprinkler valve room (1) main drain sign on boiler drain for wet system in sprinkler room (1) aux drain sign in parking space 181 on level C 2. Need to replace the following gauges: (3) water gauges in sprinkler room (2) air gauges in sprinkler room (1) water gauge in stair B,