7668 Standish Place
Rockville, MD 20855
(301) 861-0972

Our Top Cities


Job Locations
for manassas park, va


Map of Manassas Park VA
Dwayne  B.

Dwayne B.


Job Checkin

08/06 Juan 7a he is meeting you 703-568-6946 Portable Extinguishers and Kitchen Suppression Inspection ***NEW CUSTOMER 3/2018*** Annual Inspection Extinguisher Equip Desc: Inspect (6) Exts ***NEW CUSTOMER 3/2018*** Semi-Annual Inspection Kitchen Equip Desc: Inspect (1) WHDR 600 and (1) WHDR 260 Inoperable Deficiency: kidde 2.6 front hood Same deficiency’s remain from last inspection: *detection fail due to grease buildup in conduit and corner pulleys *excessive grease buildup on control head (needs replacement)** * hydro testing due on kidde 2.6 gallon cylinder * cartridge actuation pin must be replaced *outdated cartridge must be replaced parts for detection line 2 detectors 3 corner pulleys 5ft conduit 10ft vable 1.5hr labor **Customer added 2 fryers and a 1 burner range that lacks protection and detection.** Hood length: 6ft Duct:12inx12in Grill:18inx18in Fryer 1: 24inx14in Fryer 2: 24inx14in Inoperable Deficiency: 2 k-clas extinguishers are due for hydro testing