On-site for an AC maintenance with repair. Found high head pressure during test mode and discovered the condenser coil was severely impacted with dirt and lint. Cleaned it using coil cleaner and low-pressure rinse. Also noticed the contactor had burnt contacts—replaced it. Subcooling now reads 12°F and system is operating within specs.