Arrived on site for 4 system heating maintenance. Homeowner stated all was well with normal unit operation to her knowledge. Discussed surge protection with the homeowner to protect the hvac equipment. Proceeded with maintenance as scheduled. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested for gas leaks 6. Tested functionality and cleaned flame sensor 7. Tested functionality and cleaned pressure switches and ports 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Tested functionality and visually inspected surface igniter 12. Checked blower amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. Upon testing the media room unit, it was found that the blower motor was not working. Further testing revealed that the motor was receiving signal from the con

Arrived on site for 4 system heating maintenance. Homeowner stated all was well with normal unit operation to her knowledge. Discussed surge protection with the homeowner to protect the hvac equipment.  Proceeded with maintenance as scheduled. 
1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested for gas leaks
6. Tested functionality and cleaned flame sensor
7. Tested functionality and cleaned pressure switches and ports
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Tested functionality and visually inspected surface igniter
12. Checked blower amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.

Upon testing the media room unit, it was found that the blower motor was not working. Further testing revealed that the motor was receiving signal from the con Arrived on site for 4 system heating maintenance. Homeowner stated all was well with normal unit operation to her knowledge. Discussed surge protection with the homeowner to protect the hvac equipment.  Proceeded with maintenance as scheduled. 
1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested for gas leaks
6. Tested functionality and cleaned flame sensor
7. Tested functionality and cleaned pressure switches and ports
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Tested functionality and visually inspected surface igniter
12. Checked blower amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.

Upon testing the media room unit, it was found that the blower motor was not working. Further testing revealed that the motor was receiving signal from the con