Arrived on Site, powered unit on test. Unit would shut off very quickly after starting. I measured pressures, and found high superheat and low suction pressure. Tested contactor and capacitor both were testing within range. Start amps and run amps tested within range. Proceeding to the furnace I found the blower motor was not running. Tested power coming into the motor and found power making in to the motor. Measured resistance on the motor and found no resistance. Informed homeowner that we would need to order the motor first thing in the morning as the supply houses are closed right now and we would contact them tomorrow morning with more information as to when we could have this motor installed for them. Collected $200 deposit in order to get this motor on it way and process the warranty paperwork. Condenser breaker left off in order to avoid damage to the unit.