Performed maintenance on 2025 Trane Heatpump. 1. Visually inspected condenser coil for debris/ dirty. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor. 6. Checked compressor amp draw. 7. Checked condenser fan motor amp draw. 8. Inspected / replaced return filter. 9. Inspected return plenum for debris/ dirty. 10. Inspected evaporator coil. 11. Inspected blower motor/ blower wheel. 12. Checked blower amp draw. 13. Measured temperature differential from supply to return. 20 degrees measured. 14. Tested capacitor and contactor (outdoor electrical) 15. Rinsed condenser unit to promote heat exchange 16. Tested emergency heat and found no issues Measured high start amps on the outdoor unit 100+. Advised to add hard start kit to ensure compressor and related electrical components see maximum life span. The most wear and tear that gets put on these components is on the initial star

Performed maintenance on 2025 Trane Heatpump.
1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested compressor/ condenser fan motor capacitor.
6. Checked compressor amp draw.
7. Checked condenser fan motor amp draw.
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Inspected blower motor/ blower wheel.
12. Checked blower amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested capacitor and contactor (outdoor electrical)
15. Rinsed condenser unit to promote heat exchange
16. Tested emergency heat and found no issues

Measured high start amps on the outdoor unit 100+. Advised to add hard start kit to ensure compressor and related electrical components see maximum life span. The most wear and tear that gets put on these components is on the initial star Performed maintenance on 2025 Trane Heatpump.
1. Visually inspected condenser coil for debris/ dirty.
2. Inspected condenser fan motor.
3. Inspected condenser fan blades.
4. Inspected/ cleaned wiring connections.
5. Tested compressor/ condenser fan motor capacitor.
6. Checked compressor amp draw.
7. Checked condenser fan motor amp draw.
8. Inspected / replaced return filter.
9. Inspected return plenum for debris/ dirty.
10. Inspected evaporator coil.
11. Inspected blower motor/ blower wheel.
12. Checked blower amp draw.
13. Measured temperature differential from supply to return. 20 degrees measured.
14. Tested capacitor and contactor (outdoor electrical)
15. Rinsed condenser unit to promote heat exchange
16. Tested emergency heat and found no issues

Measured high start amps on the outdoor unit 100+. Advised to add hard start kit to ensure compressor and related electrical components see maximum life span. The most wear and tear that gets put on these components is on the initial star