Diagnostic/ system not cooling. Upon arrival I found the blower motor not running. I checked to see if the motor is receiving the correct 240 high voltage and the correct 24 volts for low voltage. Found the motor is receiving the proper voltage but still not turning on. The blower motor has an internal failure and will need to be replaced. I presented an estimate for labor on replacing the blower motor and it was approved. Picked up the new motor and returned to install it. Fired system off afterwards and checked component amperage’s and monitored system operations. The system is cooling properly at this time. Bryant Air Handler Model#FV4CNF003 Serial#2723F40134