Today I arrived on site and performed a summer tune-up on your system. Here's a summary of the work completed: **Indoor Unit (Air Handler in Closet):** * Replaced the 20x25 pleated filter with a spare provided by the customer. * Confirmed the indoor coil is clean and in good condition. **Outdoor Unit (Side of House):** * Verified the outdoor coil is clean and in good condition. * Tested and inspected the following electrical components, all operating within manufacturer's specifications: * Blower Motor * Compressor * Blower Run Capacitor * Condenser Fan Motor * Compressor Run Capacitor * Fan Run Capacitor * Contactor * Electrical Wiring * Inspected the blower wheel, primary drain pan, and secured electrical wires; all are in good working order. **System Performance:** * Measured a return air temperature of 76.0°F and a supply air temperature of 53.0°F. * Cleared the condensate drain line and cleaned out the primary pa