Performed and AC check on the system. Upon arrival I found the outdoor fan motor was running backwards, and the static pressure was extremely high with a return of .54. I removed the air filter and found the unit is operating with a 16 inch return and should be a minimum of an 18 for the size of the unit. The homeowners have Hot bedrooms over the garage and the master bedroom. These bedrooms have high pressure and close the doors when the unit is running. I recommended jump ducts and adding a return. I found in the attic. The insulation is in adequate and there is bat insulation that is not fully seated , the outdoor fan motor has a bad capacitor and was wired in properly. The contactor was burnt. I replaced the contactor and capacitor for the outdoor fan motor and wired it back properly. The unit is operating properly for conditions.