Charles B.

Charles B. Job Checkin

Arrived to home Set thermostat to cool Checked system operations Found following -no clean outs in drain line -blower panel missing seal -blower safety switch taped shut -coil panel not sealed -leak in Z1 supply duct -dirty blower compartment (due to seal missing) -inrush amps on compressor high -dual capacitor low -return bypass installed which is bad for single stage zone systems (should be dump zone)

Arrived to home
Set thermostat to cool
Checked system operations
Found following
-no clean outs in drain line
-blower panel missing seal
-blower safety switch taped shut
-coil panel not sealed
-leak in Z1 supply duct
-dirty blower compartment (due to seal missing)
-inrush amps on compressor high
-dual capacitor low
-return bypass installed which is bad for single stage zone systems (should be dump zone)

Charles B.

Charles B. Job Checkin

Arrived to home Checked blower - good Zoning calling for cool Checked condenser Found bad dual capacitor Start windings damaged Ducting has return bypass in lieu of dump zone Needs to be reduced to allow for better efficiency and comfort Performed following repairs Inrush kit Dual Amrad capacitor

Arrived to home
Checked blower - good
Zoning calling for cool
Checked condenser 
Found bad dual capacitor
Start windings damaged
Ducting has return bypass in lieu of dump zone
Needs to be reduced to allow for better efficiency and comfort

Performed following repairs
Inrush kit
Dual Amrad capacitor

Charles B.

Charles B. Job Checkin

Arrived to home - set thermostat to cool - checked system - found following: - bad dual capacitor (hole in body) - bad fan motor (ruptured seal) - bad inrush kit (popped) - bad contactor (burnt/pitted) Fan motor Contactor Inrush kit Dual cap *complimentary coil bath

Arrived to home
- set thermostat to cool
- checked system
- found following:
- bad dual capacitor (hole in body)
- bad fan motor (ruptured seal)
- bad inrush kit (popped)
- bad contactor (burnt/pitted)


Fan motor
Contactor
Inrush kit
Dual cap
*complimentary coil bath

Charles B.

Charles B. Job Checkin

Arrived to home Checked air flow on AHU - good Started freezing on indoor coil Low heat transfer Leak in system

Arrived to home
Checked air flow on AHU - good
Started freezing on indoor coil
Low heat transfer
Leak in system

Charles B.

Charles B. Job Checkin

I checked out equipment operations, would recommend maintenance plan to keep equipment clean and operating good.


Charles B.

Charles B. Job Checkin

Arrived to home Checked system Found existing separated CFM cap bad (had dual cap not being used was good) Sub cool low Temp split low Rust inside air handler Existing supply plenum too small Disconnect warped Air handler switch sparks when turning on (warped as well) Contactor pitted and beginning to burn Start amps excessively high


Matthew B.

Matthew B. Job Checkin

found the thermostat wasn’t fully installed onto its base. The homeowner had reset the blown breaker. I checked the units operations and it is operating within running amps and the capacitors tested good. The outdoor fan motor case temperature tested OK. The unit is suffering from excessively high starting apms, causing it to trip breaker I recommended inrush kits for both units and maintenance plans to get both units serviced


Nixa G.

Nixa G. Job Checkin

Performed cooling inspection. While on site during inspection system developed a short do to a bad thermostat. Also took out the contactor. I replaced the thermostat with a customer supplied one and the contactor was covered by us so next warranty per Alex. Once all repairs were done the inspection was completed. The system is cooling upon departure. Preferred Cool Home Membership - 1 System Includes two maintenance visits per year for 1 system Front of the line, priority service over everyone else, guaranteed service within 24 hours Discounted $37 diagnostic fee (versus regular diagnostic fee of $97) 100% of your protection plan goes toward your future system replacement (capped at $1,000) https://www.idealairaz.com/flipbook/cool-home/?page=1


Matthew B.

Matthew B. Job Checkin

Performed a membership visit and cooling. Homeowners moved forward with recommended repairs and did not have the time for me to perform them need to return and make the repairs. DESCRIPTION Includes two maintenance visits per year - 1 System Front of the line, priority service over everyone else, guaranteed service within 24 hours Discounted $37 diagnostic fee (versus regular diagnostic fee of $97) No weekend or after hour fees 100% of your protection plan goes toward your future system replacement (capped at $1,500) 10% Discount on any repair work needed $200 Discount on Home Performance upgrades https://www.idealairaz.com/flipbook/cool-home/?page=1


Charles B.

Charles B. Job Checkin

Checked system noises Compressor harmonic vibrations Transfers to structure of home System cycles every 6-9 minutes Duct is ok, supply plenum not long enough for proper location of REME Halo Has ODA duct direct from home to roof - no dampers Discussed installing line set vibration isolation Replacing with variable capacity system (Trane or Bosch) Also would like pricing on Mitsubishi multi zone mini split Justin has bad allergies


Eric  A.

Eric A. Job Checkin

Bosch heat pump install, insulation installation and removal and replacement, duct sealing in Surprise


Matthew B.

Matthew B. Job Checkin

DESCRIPTION Preferred Cool Home Membership - 1 System Includes two maintenance visits per year for 1 system Front of the line, priority service over everyone else, guaranteed service within 24 hours Discounted $37 diagnostic fee (versus regular diagnostic fee of $97) 100% of your protection plan goes toward your future system replacement (capped at $1,000) https://www.idealairaz.com/flipbook/cool-home/?page=1


Matthew B.

Matthew B. Job Checkin

Performed a membership visit in heating. Observed the unit is experiencing excessively high starting amps. Recommend installing and in rush kit to alleviate the stress on the system. The unit unit is experiencing excessively high static pressure in the ductwork and recommend an energy audit.


Matthew B.

Matthew B. Job Checkin

Full Install of REME HALO®Zero RGF’s proprietary aGHP-Cell™technology creates low level, airborne Gaseous Hydrogen Peroxide (aGHP™) throughout the air-conditioned space Reduces bacteria, viruses, odors, and mold along with allergens & dust at the source. REME HALO®Zero is verified Zero Ozone to UL 2998 https://www.youtube.com/watch?v=1ChdZMrkLeM


Camari D.

Camari D. Job Checkin