We will return to complete work once the QO 20 amp and 15 amp 240 volt GFCI breakers come in. We will install new 240 volt lines to the areas where the mini split units will be installed. We will install service disconnects on the outside of the home and provide wired whips off the disconnects that the HVAC company will tie into the new units. We will install new GFCI breakers to power and protect units. 6/8 Returned today and ran 2 new 240v circuits and installed weather resistant disconnects on the exterior of home as quoted. I installed new 240v GFCI breakers in the newer panel in the basement unfinished area. I left disconnects in the off position so that the tails will not be live until units are installed.