Eduardo  R.

Eduardo R.


Job Checkin

Confirmed appt with Kristie S via email - 908-561-8855 Email: kristie@watchungvalleygc.com Tech arrivl: 8am The following discrepancies were found during your Annual Sprinkler Inspection that needs to be corrected for Compliance: Need to perform 5 year FDC Hydro test on (1) FDC per NFPA 25 section 13.7.4. We will pressurize the piping between the FDC connection and the FDC check valve to ensure its integrity. Please note that this test may identify issues and leaks that need additional repair. This quote covers the hydro test only and any issues including but not limited to defective piping, leaks, defective FDC connections, defective FDC checks or defective/leaking fittings will be quoted and repaired separately. Also note this test introduces water into piping that normally is dry and this test is designed to identify weaknesses in the FDC piping. Any weaknesses in the piping or components will begin to leak during this test which could lead to water leaking into the building. Provis