Arrived on site, found only blower motor running without thermostat calling. Tested call for cooling unit was working as intended. Tested low voltage without thermostat calling and found no power on anything other than R. Removed thermostat from wall and unwired low voltage going to blower motor and blower would still run when high voltage was applied. This leads me to believe that the motor is shorted somewhere inside and will not turn off. This could be due to a power surge during the storms on Sunday. Left estimates for motor replacement and surge protection. Homeowner stated she would need to talk with husband in order to determine if this is the route they wanted to take. Unit in working order upon departure.