824 S Central Expressway, Suite 100
Anna, TX 75409
903-482-4900

Our Top Cities


Job Locations
for gunter, tx


Map of Gunter TX
Matthew C.

Matthew C.


Job Checkin

Performed a complete heating system maintenance and inspection. (Heat Pump) 2017 Inspected and tested all electrical components and safety controls on the indoor unit; all components tested within manufacturer specifications. Verified system temperatures: return air temperature measured at 76°F; supply air temperature measured at 102°F and rising. Confirmed air filter was recently replaced by client; filter size is 24” x 24” x 1” and 12x12x1. Inspected and tested all electrical components on the outdoor unit; capacitors failed out of manufacture specifications, 65.3/70 and 4.9/7.5. Client elected to have capacitor changed under warranty. Also the units compressor was starting up over 100 amps manufacturer limit is 144 amps. Client elected to have that revisited on the spring visit. Confirmed system was operating properly and heating upon departure. System Status: Operating normally at time of service.

Performed a complete heating system maintenance and inspection. (Heat Pump) 2017

Inspected and tested all electrical components and safety controls on the indoor unit; all components tested within manufacturer specifications.


Verified system temperatures: return air temperature measured at 76°F; supply air temperature measured at 102°F and rising.

Confirmed air filter was recently replaced by client; filter size is 24” x 24” x 1” and 12x12x1. 

Inspected and tested all electrical components on the outdoor unit; capacitors failed out of manufacture specifications, 65.3/70 and 4.9/7.5. Client elected to have capacitor changed under warranty. Also the units compressor was starting up over 100 amps manufacturer limit is 144 amps. Client elected to have that revisited on the spring visit. 

Confirmed system was operating properly and heating upon departure.

System Status: Operating normally at time of service. Performed a complete heating system maintenance and inspection. (Heat Pump) 2017

Inspected and tested all electrical components and safety controls on the indoor unit; all components tested within manufacturer specifications.


Verified system temperatures: return air temperature measured at 76°F; supply air temperature measured at 102°F and rising.

Confirmed air filter was recently replaced by client; filter size is 24” x 24” x 1” and 12x12x1. 

Inspected and tested all electrical components on the outdoor unit; capacitors failed out of manufacture specifications, 65.3/70 and 4.9/7.5. Client elected to have capacitor changed under warranty. Also the units compressor was starting up over 100 amps manufacturer limit is 144 amps. Client elected to have that revisited on the spring visit. 

Confirmed system was operating properly and heating upon departure.

System Status: Operating normally at time of service.