Installed Custom Comfort mini-split system utilizing existing electrical supply and refrigerant line sets. System was pressure tested with nitrogen to 400 PSI and held for 30 minutes with no pressure loss observed. Evacuated system to below 251 microns and verified acceptable decay. System was started up and tested; all components are operating properly at this time. We were unable to remove old unit we will return at a later date to to remove.