Alex W.

Alex W.


Job Checkin

I removed 200 amp seu cable due to it being crack and at that point it allows water to flow through the sheathing into the electrical panel I replaced it with a new 200 amp SEU cable I ran a new cold water ground from the main electrical panel to outside then drilled back into the home under the steps and connected my #4 ground wire to the mater water pipe within 5 feet of the entrance of the water line I bonded the home at the water heater I installed 2 8 foot ground rods outside of home. They are 6 feet apart then i ran a #4 ground wire from one to the other then into the electrical panel in a continuous loop I separated all the grounds and double tapped neutrals according to the national electrical code All neutrals are under their own screw terminals I installed a add a lug for the oven circuits neutral I installed a ultra whole home surge protector and installed a 2 pole 50 amp qo square d electrical breaker to power the surge protector. This surge protector was installed