-Warranty Contactor -Warranty Capacitor - 5-2-1 Hard Start Kit Upon arrival i installed warranty capacitor 45/5. Installed warranty Contactor single pole Installed 5-2-1 hard start kit. Tested all electrical to make sure they were testing correctly for the manufacture. All tested within manufacturer specifications. I tested start amps on the unit yesterday 9/29/25 and was reading 50 amps on start up after installing the hard start kit on 9/30/25 i was reading the start up amps at 31 amps. Unit was cooling upon departure.

-Warranty Contactor
-Warranty Capacitor
- 5-2-1 Hard Start Kit

Upon arrival i installed warranty capacitor 45/5.
Installed warranty Contactor single pole
Installed 5-2-1 hard start kit.

Tested all electrical to make sure they were testing correctly for the manufacture. All tested within manufacturer specifications. I tested start amps on the unit yesterday 9/29/25 and was reading 50 amps on start up after installing the hard start kit on 9/30/25 i was reading the start up amps at 31 amps. Unit was cooling upon departure. -Warranty Contactor
-Warranty Capacitor
- 5-2-1 Hard Start Kit

Upon arrival i installed warranty capacitor 45/5.
Installed warranty Contactor single pole
Installed 5-2-1 hard start kit.

Tested all electrical to make sure they were testing correctly for the manufacture. All tested within manufacturer specifications. I tested start amps on the unit yesterday 9/29/25 and was reading 50 amps on start up after installing the hard start kit on 9/30/25 i was reading the start up amps at 31 amps. Unit was cooling upon departure.