Upon arrival the customer stated the inside blower was working and the outside equipment was off. We proceeded inside to the unit in the attic to check the float switch to ensure it was not tripped. No evidence that it had been tripped. We proceeded outside to check outdoor equipment. We noticed that the thermostat wires were cut potentially from the lawn care personnel. Connected wires back together. Preformed cooling maintenance checked all electrical components inside and outside. All tested within manufacturer specifications. Tested start and runs amps of compressor and fan motors. All tested within manufacturer specifications temp split across the coil is 18 degrees. Unit was cooling upon departure.