41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Local Reviews
for temecula, ca

Rated 4.9 out of 5 stars based on 514 customer reviews

Great Job

Jimmy and Evan did a great job. They were very professional, detailed, clean work site and took their time with any comments or recommendations. Awesome job guys.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

Very professional

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Outstanding Service

Highly skilled and professional. Michael is an exemplary employee, he is courteous, knowledgeable, and attentive to detail regarding repairs and service.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Jimmy Garcia is the man and was super helpful and informative

  • Overall Experience
  • Quality
  • Price
  • Convenience

great service

well knowledge and gave advice wisely.

  • Overall Experience
  • Quality
  • Price
  • Convenience

A.Gorman - Service Review

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Amazing customer service. They know people

Above and beyond other companies. Whoever is in charge is in it for the long haul, they understand customer service. The service tech today was incredible.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Nice guy

Jimmy explained things well and was very polite.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great follow-ip

Had some issues with the new control panel for our unit, but Michael showed up and quickly resolved those issues. Everything is resolved and working well

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service

Excellent, the tech was thorough.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Customer service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for temecula, ca

Jimmy P.

Jimmy P. Job Checkin

Arrived on site to perform AC maintenance on 2014 condensing unit. Upon arrival homeowner stated that system has been working fine and has no questions at this time. Performed deep cleaning and electrical check on unit. Electrical components checked out properly although refrigerant pressures were looking abnormal. Charge system up with approximately 1 pound of refrigerant system did not react properly due to thermal expansion valve having restriction. Advised client TXV will need to be replaced and she will be available June 10 for the repair. Upon departure system is operational.


Jimmy P.

Jimmy P. Job Checkin

Arrived on site to preform Ac maintenance on 2019 Lennox system.


Nathan G.

Nathan G. Job Checkin

The system qualifies for an 18 months no payments no interest or Reduced interest at 111 per month


Jimmy P.

Jimmy P. Job Checkin

Arrived on site to perform AC diagnostic on 1994 Condenser. Upon arrival Jed stated that he moved in approximately a year ago and just noticed on Saturday that the thermostat is saying no power to the R wire. Proceeded to indoor furnace inside of garage and immediately opened the electrical panel inside the blower compartment and found that the low-voltage wire connecting to the transformer has disconnected. Adjusted wire and system began to fire up. Although system was in very bad shape and found that filter was heavily clogged up and indoor blower motor has oil leakage and severe dust buildup inside of it. Proceeded to outdoor condensing unit and found That the compressor amperage was very high and on the brink of over amping and only getting higher, considering that today is fairly cool day this is an indication it is over working. Measured duel secondary motor control rating and found that it was rating 38+5 and on the brink of the becoming weak. Starter was also severely burnt and


Madison H.

Madison H. Job Checkin

Upon arrival found the unit making a noise. Diagnosed it as the fan motor. System is currently operational. Client will deal with the sound. Unit is operational upon departure.


Luis M.

Luis M. Job Checkin

Upon arrival performed maintenance on brand new high efficiency unit. Merv 16 filter is in very good condition. Indoor motor & wheel in range. Circuit board & electrical connections good. Amperage’s throughout system are very good. Electrical fuses good. Thermostat in working order. Removed 1 inch filter since system already has a 5 inch filter. System is operational upon completion.


Luis M.

Luis M. Job Checkin

Technician found an area on the condenser coil to be very torn up where it’s only the copper showing and the aluminum fins are gone. Both the fan motor and condenser motors are leaking a ton of oil and seizing up. The refrigerant levels (R22) were a few pounds undercharged, there may be a pinhole leak in the system somewhere. The collars where the ducts connect are not sealed and are leaking air. Most of the air registers were extremely dirty from the air coming out of the ducts meaning the indoor blower compartment is very dirty. The compressor and the motors are drawing a lot of power resulting in the customer’s high energy bill.


Jorge C.

Jorge C. Job Checkin

Check System Static Pressures Check all Safety and Limit Switches Clean Condenser Coil Duct Leakage Inspection Remove Debris from the Condenser Check Refrigeration Pressures Perform Visual Inspection and Clean Service Panel Measure Starting Amperage of the Compressor Tighten Electrical Connections Measure System Amperage and Voltage Flush Condensate Drain Lines Measure Temperature Difference Vacuum Furnace Return Air Grille Clean in Place Blower Compartment Inspect Blower Wheel for Proper Balance Monitor Air Purification System Apply UV Protective Coating on Condenser Perform Energy Usage Calculation Test Condenser Pressure Switches Check Thermostat for Proper Operation / Calibration


Michael P.

Michael P. Job Checkin

Performed spring tune up on Lennox system. Measured cooling temperature split. Verified refrigerant charge. Tested electrical components. Recorded motor draws. Cleaned outdoor coils. Replaced air filter.


Jorge C.

Jorge C. Job Checkin

Performed maintenance on 2004 trane system. Cycled system for cooling. Checked indoor unit electrical and system components. Temperature split is in range. Unit has no safety switch on condensation lines. Homeowner will be replacing his own filters. Checked outdoor unit electrical and system components. Amp draws and starting amps on compressor are high. Condenser fan motor amps are also high. Primary motor control in good condition, secondary motor control is within range. Pulled condenser motor and thoroughly washed out condenser coil inside and out. Went over findings and recommendations with homeowner. Mentioned we have gone over everything every time we come out but it is still working, wishes to hold off on any repairs. System is operational upon departure.


Jimmy G.

Jimmy G. Job Checkin

Arrived on site to perform spring tune up on a 2 20 year old unit. Both condenser are located in back yard. Furnace located in attic. Client stated no issue and is cooling. Washed condenser coil inside and out. Checked both electrical compartment. Checked both primary Staters and are okay. Both secondary motor controls are good and have been replaced in past. Fan motor are good but are working hard as over all conditions of units are old and using a lot of power. Both fan motor are in range but have a bit of oil. Checked start up and run amps both start up amps on compare good as they got booster kit added on. Found run amps to be high as both are pulling 16 amps at 82 degrees outside. Max is 21. Advised at 100 degrees outside those number can go up and compressor is pulling alot of power. Advised units are on borrowed time. Both units hold R-22 and found the smaller unit to be low and not cooling as low side is at 40 and the other unit is hold a good charge as low use is at 67 and coo


Jimmy P.

Jimmy P. Job Checkin

Arrived on site to perform AC diagnostic on 1999 condensing unit. Upon arrival Noel stated that the system is working but keeps tripping his breaker. Began diagnostic at thermostat and found an indoor unit was operational. Proceeded to outdoor condensing unit and found the Condenser did turn on. Measured refrigerant pressures and found that they were in range although contained a phased out refrigerant called R 22 which is no longer manufactured. Once I began measuring Amperages for the compressor I found that it was using a total of 26 A which is way too high considering the max amperage is rated at 28 A. Outdoor Fan motor is also over amping. Noel has already replaced himself the duel secondary motor control and the indoor blower motor inside of the house. At this time it is a parent that the compressor is over amping and on its last leg till it breaks down. Advised Noel that a R22 compressor replacement will be a major repair on a 1999 unit and is only temporary. Both homeowners are


Ashley G.

Ashley G. Job Checkin

Check System Static Pressures Check all Safety and Limit Switches Clean Condenser Coil Duct Leakage Inspection Remove Debris from the Condenser Check Refrigeration Pressures Perform Visual Inspection and Clean Service Panel Measure Starting Amperage of the Compressor Tighten Electrical Connections Measure System Amperage and Voltage Flush Condensate Drain Lines Measure Temperature Difference Vacuum Furnace Return Air Grille Clean in Place Blower Compartment Inspect Blower Wheel for Proper Balance Monitor Air Purification System Apply UV Protective Coating on Condenser Perform Energy Usage Calculation Test Condenser Pressure Switches Check Thermostat for Proper Operation / Calibration


Jimmy G.

Jimmy G. Job Checkin

Arrived on site to perform spring tune up on a 21 year old unit. Condenser located in the back yard. Client stated no issues as she knows unit is old. Washed condenser coil inside and out. Primary stater okay just work out and burnt up. Found secondary motor control out of range on the compressor. Fan motor is leaking and pulling 1.3 as max is 1.4. Checked start up and run amps. Start up is high but in range. Would recommend compressor booster kit to prevent hard start up. Found unit with no protection. Checked pressure and unit is holding a charge just not running efficient. Unit is hold charge of R-22 and is no longer in production. Inspected indoor unit filter okay recommended keep some on hand. Blower assembly is dirty. Motor has been leaking a lot of oil as unit is zoned and only has a single stage unit. Advised unit is on borrowed time. unit is cooling at 22 degrees. No protection on unit snide and found no safety over flow switches on lines. Drain lines have debris but okay as


Jimmy G.

Jimmy G. Job Checkin

Arrived on site to perform diagnostic on a no cooling 2006 weather king. Spoke to client and he stated unit works but at time unit would show error issue for the cooling wire. Inspected unit cycled cooling and ran for a bit and shit off showing error code. Opens up unit and inspected electrical thermostat wires are good and correct. Jump unit at board and ran good and did not stop. Jumped at the thermostat bypass thing old nest and unit was operational as well. Advised client issues is the best thermostat.put in a tester theme and unit was operational and did not shut off due to any wire issues. Advised client would perform a system evaluation to see over all conditions. He was okay with soo. Found blower wheel hammer of dirt and oil. Motor has been leaking in past and can fail due to age and condition. Secondary motor control is out of range for blower and can fail in future. Found big burn spot on electrical circuit board and advised is not good at all and board can get fried up as n