Responded to a no cooling call on a Goodman GSX160361 air conditioner. Checked capacitor with a meter and found the dual run capacitor shorted. Replaced faulty 35/5 MFD capacitor with new Titan Pro replacement. Verified proper operation of compressor and condenser fan motor after new capacitor install. Performed unit cooling cycle test, measuring 22°F superheat and 10°F subcooling within expected parameters. Recommended customer schedule annual preventative maintenance to help extend equipment life. Provided quote for capacitor and labor.