DESCRIPTION Recovery Refrigerant & Check Charge Follow EPA guidelines to recovery excess refrigerant from system Let system stabilize and check pressure until system is within manufactures specifications Overcharged systems will have a decreased lifespan due to higher head pressure in the compressor Non Members: 90 day parts + labor warranty on all repairs Cool home members: 2 year parts + labor warranty on all repairs Thaw out coil Once excess refrigerant was removed and coils were thawed out refrigerant pressures were revised once again. System appears to have a liquid line restriction. Base repair recommended is to replace txv and add new refrigerant to ensure non condensibles are present. This does not guarantee there could be other underlying issues. Once initial repair is completed the system can be re evaluated if needed. Due to age of system it is also advised to consider new install of equipment. System cooling at its best capacity at departure.