Performed an inspection on the system. The unit is a 2006 and has r22 Freon. The outdoor fan motor is not installed correctly and needs the leads secured. The contactor switch is burnt and needs replaced and the defrost control board is not operating and needs replaced. The condensate line is clogged and the unit is overflowing into the emergency pan. The inside of the cabinet is rusted from the condensate issue over a long period of time. The unit is only producing an 18° split at the unit.