Checked both systems West system Drain was 100% plugged Cleared drain with CO2 and shop vac Low on refrigerant Fan motor failing After adding refrigerant SC went from 3.4 to 8.3 with MFG spec at 10 +/- 3 East system running within mfg specs at this time Cleaned both condensers Waived coil cleaning and drain flush charge with membership