The main living room area was hotter than the rest of the house. The units weren’t going into second stage and ramping down. I adjusted the thermostats and zone control to enable to stage operations. I checked operations at the condenser and found the condenser wouldn’t rise higher than 31 hertz. The Air balance valve for the zoning was closed and not operating. I adjusted the valve. I adjusted the condenser strategy for indoor coil cooling. I disabled the DATS sensor on the zoning system. When only one zone is calling it will drop below the DATS set point. I adjusted the temperature offset on the living room Bosch thermostat.