Arrived to home Set all thermostats to cool Tested all furnaces Checked all indoor capacitors Checked all temp splits Checked all condenser capacitors Checked all amps Checked all inrush amps Checked all pressures Found following Garage system: Has restricted TXV - needs to be replaced Has high inrush amps on start Kennel area system: Has low blower capacitor System #3: Has high inrush amps Compressor Capacitor Valves starting to go on compressor - audible chattering from compressor while running System #4: Has high inrush amps All systems: No clean outs on drain lines to flush and clear traps/lines Garage and Kennel: No float switches in place to protect from water leakage