Matthew B.

Matthew B.


Job Checkin

The unit had a bad zone control motor for zone one. The outdoor fan motor is leaking oil and is overheating. This motor is intermittently, shutting down, causing the compressor to overheat and shut down. This chain of events has now damaged the capacitor for the compressor and outdoor fan motor. The unit is suffering from excessively high, starting amperage due to it being a single stage system in a three zone, the compressor needs an in rush device with a compressor delay relay Platinum Cool Home Membership - 1 System Includes two maintenance visits per year Front of the line, priority service over everyone else, guaranteed service within 24 hours Discounted $37 diagnostic fee (versus regular diagnostic fee of $97) No weekend or after hour fees 100% of your protection plan goes toward your future system replacement (capped at $1,500) 10% Discount on any repair work needed $200 Discount on Home Performance upgrades https://www.idealairaz.com/flipbook/cool-home/?page=1