Nixa G.

Nixa G.


Job Checkin

Master bedroom is warmer than usual, not maintaining room temp. Verified system had a 20 degree split, the rest of the home is keeping up. Current system has 4 zones. After testing each zones airflow, the amount delivered to the master has been increased by 5%, it is now at a total of 35%. I have explained to the homeowners the adjustments to the settings that are done on today’s visit. I have also explained to him that this can be something we can help on the back end if extra tweaking is needed to dial in airflow output. They will call the office is further assistance is needed. If issue persist and an onsite visit is needed pertaining todays service visit, the fee will cover the xtra visit if same issue. System is cooling at departure.

Master bedroom is warmer than usual, not maintaining room temp. Verified system had a 20 degree split, the rest of the home is keeping up. Current system has 4 zones. After testing each zones airflow, the amount delivered to the master has been increased by 5%, it is now at a total of 35%. I have explained to the homeowners the adjustments to the settings that are done on today’s visit. I have also explained to him that this can be something we can help on the back end if extra tweaking is needed to dial in airflow output. They will call the office is further assistance is needed. If issue persist and an onsite visit is needed pertaining todays service visit, the fee will cover the xtra visit if same issue. System is cooling at departure.