Arrived to home Discussed issues with Chuck Thermostat showed warning of excessive run time with rise in temperature Reset and verified system calling Checked condenser Fan amps good Dual cap good Compressor amps low Checked pressures Extremely low suction and normal discharge Noticed suction line freezing Went to attic Found blower not running Checked blower - 120V to motor - no control voltage to module Bad PCB Also noticed overflow switch disengaged Ducting incorrect for 3 zone single stage system Sent estimates for both