I checked over the unit. It is operating within amp ratings and is producing a 21° temperature split. The gauge readings match the charge charts on the system. The only issue I found is the outdoor fan motor is a 1075 and the original motor is an 825. The outdoor fan motor also shows signs of bearing failure and could be shutting down during the part of the day.