Performed cooling inspection. Inspected coils for any signs of leakage and none found. Refrigerant pressures are on the lower end of the designed range but are within it. Compared to last visit and are about the same. Today’s sub cool was 7 degrees and the temperature split was 18 degrees. System working within specifications at this time.